Compartments Current Transformer Current transformer protects the system by sensing any abnormal current in the line and measuring the usual conductive current. Insulation by high-voltage is not required since this is in the enclosure grounded at both ends of the circuit breaker and isolated by the first conductor and SF6 gas. Voltage Transformer Voltage transformer is a small- sized transformer using high- reliable gas insulated winding. It monitors the voltage of the line or the busbar. Voltage transformer is classified into two types: Metering Out Fit (MOF) and general meters. Lightning Arrester The lightning arrester protects the power utilities from overvoltage due to lightnings or surges and prevents the utilities from breakdowns and blackouts. It uses Zine-Oxide Lightning Arrestor (ZLA) which removes the series gap using Zinc Oxide element.
I 10 11 Gas Insulated Switchgear Interfaces The interface is classified into three types: ①Gas-to-Oil Bushing: when the interface is directly connected to the transformer, the bushing separates the gas and insulation oil. The bellows compensates the tolerance and minimizes vibration. ②Gas to Air Bushing: when the interface is directly connected to the feeder, the bushing filled with the SF6 gas is used. ③Cable Sealing End: when the interface is directly connected to power cable Cable Sealing End ❶Cable ❷Epoxy Cone ❸SF6 Gas ❹Shield ❺Tulip Contact ※ Adheres to IEC 60859 Gas-to-Oil Bushing ❶Bellows ❷Conductor ❸SF6 Gas ❹Tulip Contact ❺Transformer Bushing ❻Transformer Oil ※ Adheres to IEC 61639 Gas-to-Air Bushing ❶Terminal ❷Upper Shield ❸Bushing ❹Conductor ❺SF6 Gas ❻Internal Shield ❼Tulip Contact