Technical Specification Environmental PARAMETER VALUES PARAMETER VALUES (Compound) (Measurement range) (Compound) (Measurement range) Hydrogen (H ) 5 - 5,000 ppm Temperature 2 -40 to 55°C (-40 to 131°F) Carbon Range 2 - 50,000 ppm Monoxide (CO) Oil Temperature -40 to 120°C (-40 to 248°F) Carbon Dioxide Range 20 - 50,000 ppm (CO ) 90 - 250 VAC; 47 - 63Hz; 2 Power Supply 150W (8A max) Methane (CH ) 2 - 50,000 ppm 4 Operating Acetylene (C H ) 0.5 - 50,000 ppm 10 - 95% RH non-condensing 2 2 Humidity Ethane (C H ) 2 - 50,000 ppm 2 6 Enclosure IP55 Ethylene (C H ) 2 - 50,000 ppm 2 4 Water (H O) 0-100% RS (given in ppm) Weight 78 kg (172 lbs) 2 Oxygen (O ) 150 - 50,000 ppm, ±10% 2 Single Phase NO and NC provided, 5A 250 Nitrogen (N ) 10 – 130,000 ppm, ±15% Alarm Relays VAC, 5A 30 VDC. 2 1± 5% or ± LDL Measurement Variable - 1 per hour Accuracy** (whichever is greater) Frequency to 1 every 4 weeks ** Accuracy quoted is the accuracy of the detectors during calibration. System Configuration Sensor Servers Clients Substation 1 TCP/IP Networks Clients Shared Memory Clients I/O Driver Clients App Server TCP/IP DB Server TCP/IP Clients Substation 2 Clients Substation n
Portable UHF PD Monitoring System for Transformer HiCMS TM-100 The HiCMS TM100 is the portable UHF PD analyzer suitable for monitoring of PD activity in transformer. This device detects and records the UHF PD signal generated by defects in the transformer without outage. Using the Hyosung’s unique algorithm, TM 100 determine the defect cause and location, then it will provide the early warning of unexpected failure before complete breakdown occurs. Features •PartialDischarge(PC)measurementforeachcompartmentoftransformer. •AnalysisalgorithmtoclassifybothPDandbackgroundnoise.•LocationestimationofPartialDischargepositionintransformer using the time of flight method. •Convenientandhandythroughlightweight,compactsizeand battery operation. •Fullyprotectedagainstsurgeandtransientovervoltage Specification Item Specification Detection bandwidth 300 ~ 1,500MHz Input signal level -85 ~ 0dBm No. of Input channel 4ch Sensor type Monolpole type sensor Sensor install position Drain valve Supply voltage 90 ~ 264VAC / 50 ~ 60Hz Synchronization PT signal or internal Operation temp. -25 ~ 55℃ Weight about 20kg Case dimension 411 x 322 x 168mm I 18 19 HiCMS Hyosung intelligent Condition Monitoring System