Transformer Condition Monitoring Solution • Monitor DGA, PD, OLTC, Total WTI/OTI, Fan/Pump Monitoring condition, hot spot etc. System • Provide accurate diagnosis result and alarm TM-2000 • Monitor 8 critical gases On-line • Diagnosis based DGA on unique algorithm System TM-200 • High sensitive On-line on-line PDM solution UHF PDM • Location System estimation of PD TM-1000 • Rapid and easy Portable application on-site PDM • Location estimation of PD Device TM-100
GIS Monitoring & Diagnosis Solution On-line GIS Total Monitoring System HiCMS GM-3000 UHF PD | Lightning Arrester Degradation Monitoring | SF Gas Density | Operating Characteristics of CB 6 Items Specification Note Operating Temperature -25 ~ 60℃ Operating Humidity 10 ~ 90% Number of PD Input Channel 9ch Detection Frequency Bandwidth 100~2,000MHz Detection Sensitivity Less than 1pC Calibration Signal 1GHz, -50dBm Watch dog for RF module Analog : 9ch, 4 ~ 20mA Gas density and Analog / Digital Module Digital : 4ch, dry contact CB monitoring SIO Module RS-485, 4ch LA monitoring Size 19 inch / 4U System Configuration UHF PD Sensor Equipment Fault Diagnosis DAU for GIS HMI CB Operation Sensor Operating 100Mbps Workstation Fiber Switched Ethernet GDT • IEC 61850 Sensor • DNP • Modbus • PD : 3/6/9ch Web Server • ADI : AI 9ch, DI 4ch/board • AI : 8ch/board • SIO(RS-485) : 4ch/board * Max 6 board is applicabl Lightning Arrester Sensor • PD : 3/6/9ch • ADI : AI 6ch, DI 6ch/board 06 I 07 HiCMS Hyosung intelligent Condition Monitoring System • AI : 8ch/board • SIO(RS-485) : 4ch/board * Max 6 board is applicabl