메뉴 건너뛰기
페이지 확대

GIS Monitoring & Diagnosis Solution On-line GIS Total Monitoring System HiCMS GM-3000 UHF PD | Lightning Arrester Degradation Monitoring | SF Gas Density | Operating Characteristics of CB 6 Items Specification Note Operating Temperature -25 ~ 60℃ Operating Humidity 10 ~ 90% Number of PD Input Channel 9ch Detection Frequency Bandwidth 100~2,000MHz Detection Sensitivity Less than 1pC Calibration Signal 1GHz, -50dBm Watch dog for RF module Analog : 9ch, 4 ~ 20mA Gas density and Analog / Digital Module Digital : 4ch, dry contact CB monitoring SIO Module RS-485, 4ch LA monitoring Size 19 inch / 4U System Configuration UHF PD Sensor Equipment Fault Diagnosis DAU for GIS HMI CB Operation Sensor Operating 100Mbps Workstation Fiber Switched Ethernet GDT • IEC 61850 Sensor • DNP • Modbus • PD : 3/6/9ch Web Server • ADI : AI 9ch, DI 4ch/board • AI : 8ch/board • SIO(RS-485) : 4ch/board * Max 6 board is applicabl Lightning Arrester Sensor • PD : 3/6/9ch • ADI : AI 6ch, DI 6ch/board 06 I 07 HiCMS Hyosung intelligent Condition Monitoring System • AI : 8ch/board • SIO(RS-485) : 4ch/board * Max 6 board is applicabl

Components HMI •HMIisaninterfacedisplaywherevariouspiecesofinformationobtained from the field is transmitted via communication with the station controller; various data and trends are displayed; obtained information is categorized into databases; equipment condition/status is diagnosed via diagnostic algorithms; equipment service life is forecast and monitoring schedules are proposed based on data analysis; malfunctioning areas are indicated during an accident; and solutions to eliminate failure are suggested. HMI is the state-of-the-art diagnostic solution that combines the latest computing and digital technologies. Station Controller (Main Unit) •Thestationcontrollerreceivesequipmentcondition-monitoringdatafrom the DAU (Data Acquisition Unit) which compiles raw data measured from the sensors installed in the field, and transmits the information to upper-tier HMI through the internal communications controller. » Offers system redundancy » Provides easy-to-use interface with other facilities, through multi-protocols •Thestationcontrollerconvertsandprocessesthedatacollectedfrom the communication controller and transmits them to upper-tier HMI. It also analyzes the control instructions from upper tiers and delivers them to lower-tier DAU. » Configures individual communication channels between lower-tier systems » Enables peer-to-peer communication between upper-tier and lower-tier systems, respectively, and allows self diagnosis » Controls communication error (critical data backup and restoration) » Connects to Ethernet (10/100 Mbps) and serial devices (RS-232/422/485) » Supports multi-protocols (e.g., DNP 3.0, Modbus, Modbus Tcp) » Allows system database downloading from upper-tier hosts » Offers system stability through redundancy » IEC 61850 Protocol is applicable ( ) DAU Local Unit •Basedondiagnosticalgorithmsoptimizedforthetransformer/GIS,DAU attains data from various sensors and delivers the information needed for alarm and diagnosis. » Adopts high-performance DSP chip and conducts high-speed real-time A/D conversion » Stores data for 24 hours during a communication failure » Capable of optic and serial (RS-232/422/485) communication » Detects problems and issues alarms in accordance with its internal algorithm » Capable of integration monitoring of various sensors is possible

탐 색

메 일